s7-tap
S7comm read-first telemetry via the ot-aiops MCP server, using pyS7 (pure Python, ISO-on-TCP / RFC1006 — no native libsnap7). Preview — validated against a mocked client, NOT live PLCs. S7-300/400/1200/1500 and compatible clones.
When to use
- A Siemens/仿西门子 PLC reachable over S7comm (
host:102,rack/slot). - Read DB/M/I/Q; check CPU run/stop.
When NOT to use (routing)
- OPC-UA →
opcua-tap; Modbus →modbus-tap; Mitsubishi →mc-tap; CNC →mtconnect-tap; MQTT/UNS →sparkplug-tap; cross-protocol triage →industrial-diagnostics. Rockwell/Allen-Bradley → not yet (ethernetip_statusroadmap stub). IT/network/Kubernetes/hypervisor/backup → not this tool.
Read tools
| Tool | Params | Returns |
|---|---|---|
s7_cpu_info |
endpoint? |
{cpu_status, cpu_info{module,serial,version}} |
s7_read_area |
area(DB|M|I|Q), dtype, start, endpoint?, db=0, count=1, bit=0 |
{items:[{address,value}]} |
s7_read_db |
db, dtype, start, endpoint?, count=1 |
{items:[{address,value}]} |
s7_read_many |
addresses[] (pyS7 strings), endpoint? |
{items:[{address,value}]} |
dtype ∈ BIT, BYTE, WORD, INT, DWORD, DINT, REAL, LREAL, CHAR.
Example: s7_read_db(db=1, dtype="REAL", start=4, count=2) →
{"items":[{"address":"DB1,REAL4","value":20.5}, ...]}
Write tool (HIGH risk · MOC · off by default)
s7_write_db(db, dtype, start, value, endpoint?, dry_run=true)
- OT-DANGEROUS. 未经授权勿对生产控制系统写入. Defaults to
dry_run=true(preview only). Captures the BEFORE value and records an undo descriptor. - To apply: set
dry_run=falseAND record an approver viaOPCUA_AUDIT_APPROVED_BY(+OPCUA_AUDIT_RATIONALE). CLI:ot-aiops s7 write-db 1 INT 0 42 --apply(double-confirm prompt). - Dry-run returns
{dry_run:true, before, would_write, note}; applied returns{applied:true, before, written, _undo_id}.
Setup
ot-aiops init (s7: host/port/rack/slot) · ot-aiops doctor · ot-aiops mcp.
S7-1200/1500 default rack 0 / slot 1; S7-300/400 often rack 0 / slot 2. The CPU
must "Permit access with PUT/GET". 缺功能提 issue/PR 欢迎留言.