ethernetip-tap
EtherNet/IP (CIP) read-first telemetry for Allen-Bradley Logix controllers via the ot-aiops MCP server, using pycomm3 (pure Python — no native deps). Preview — validated against a mocked LogixDriver, NOT a live controller.
When to use
- A Rockwell/AB ControlLogix / CompactLogix / GuardLogix controller reachable
over EtherNet/IP (TCP 44818):
host+slot(0 for CompactLogix; the CPU slot for a ControlLogix chassis). - Discover the controller's tags, read tags/arrays by name, identify the controller.
When NOT to use (routing)
- OPC-UA →
opcua-tap; Modbus →modbus-tap; Siemens S7 →s7-tap; Mitsubishi →mc-tap; CNC →mtconnect-tap; MQTT/Sparkplug/UNS →sparkplug-tap. - Cross-protocol triage →
industrial-diagnostics; OEE/asset analytics →industrial-analytics. - PLC-5 / SLC-500 (PCCC) / Micro800 → not supported (roadmap).
- IT/network/Kubernetes/hypervisor/backup → not this tool.
Read tools
| Tool | Params | Returns |
|---|---|---|
eip_controller_info |
endpoint? |
{host, slot, controller:{vendor, product_type, product_code, revision, serial, product_name, name}} |
eip_list_tags |
endpoint? |
{tag_count, tags:[{name, data_type, tag_type, structure, dimensions}]} |
eip_read_tag |
tag, endpoint? |
{tag, value, type, error, good} |
eip_read_many |
tags[], endpoint? |
{count, items:[{tag, value, type, error, good}]} (auto multi-packet) |
eip_list_tags is the headline pycomm3 capability — the controller advertises its
symbol table, so you can enumerate tags without prior knowledge. Program-scoped
tags appear as Program:<prog>.<tag>; array elements read as Array[3].
Example: eip_read_tag(tag="Conveyor.Speed", endpoint="cell5") →
{"tag":"Conveyor.Speed","value":1500.0,"type":"REAL","error":"","good":true}
Write tool (HIGH risk · MOC · off by default)
eip_write_tag(tag, value, endpoint?, dry_run=true)
- OT-DANGEROUS. 未经授权勿对生产控制系统写入. Defaults to
dry_run=true(nothing written). Captures the BEFORE value (read-back) and records an undo descriptor so the change is reversible. - Apply:
dry_run=falseand setOPCUA_AUDIT_APPROVED_BY(a recorded approver — MOC). CLI:ot-aiops eip write-tag Setpoint 42 -e cell5 --apply(double-confirm prompt).
CLI
ot-aiops eip info -e cell5 # controller identity
ot-aiops eip tags -e cell5 # tag discovery
ot-aiops eip read "Conveyor.Speed" -e cell5
ot-aiops eip read-many Speed Temp -e cell5
ot-aiops eip write-tag Setpoint 42 -e cell5 # dry-run preview
ot-aiops eip write-tag Setpoint 42 -e cell5 --apply # double-confirm
Setup
ot-aiops init (ethernetip: host/slot/port) · ot-aiops doctor · ot-aiops mcp.
Config: ~/.ot-aiops/config.yaml (protocol: ethernetip or alias eip). Test
against a CIP/Logix simulator. Endpoint text is sanitized; every tool runs through
the ot-aiops governance harness (audit/budget/risk-tier). 缺功能提 issue/PR 欢迎留言.